Publication 1734-IN058B-EN-P - June 2005
Installation Instructions
POINT I/O 24V dc Expansion Power Supply
Catalog Number 1734-EP24DC, Series B
Inside . . .
For See Page
Important User Information 2
Preventing Electrostatic Discharge 3
Environment and Enclosure 4
North American Hazardous Location Approval 5
European Hazardous Location Approval 6
About the Power Supply 8
Install the Power Supply 9
Remove the Power Supply 10
Replace the Power Supply 10
Wire the Power Supply 11
Specifications 16
Przeglądanie stron 0
1 2 3 4 5 6 ... 19 20

Podsumowanie treści

Strona 1 - Installation Instructions

Publication 1734-IN058B-EN-P - June 2005Installation InstructionsPOINT I/O 24V dc Expansion Power SupplyCatalog Number 1734-EP24DC, Series BInside . .

Strona 2 - Important User Information

10 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 20051. Pull up on the RTB removal handle to remove the terminal bloc

Strona 3 - ATTENTIO

POINT I/O 24V dc Expansion Power Supply 11Publication 1734-IN058B-EN-P - June 20051. Remove the module to the right of the power supply from its b

Strona 4 - Environment and Enclosure

12 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 200512/24Vdc WiringNC = No ConnectionCHAS GND = Chassis GroundC = Co

Strona 5

POINT I/O 24V dc Expansion Power Supply 13Publication 1734-IN058B-EN-P - June 2005Example of Continuing PowerConnect Terminal Terminals (for conti

Strona 6 - IMPORTANT

14 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005Example of Functional Partitioning1r1734adn4AdapterStatusDeviceN

Strona 7

POINT I/O 24V dc Expansion Power Supply 15Publication 1734-IN058B-EN-P - June 2005Example of Logical Partitioning1r1734adn4AdapterStatusDeviceNetS

Strona 8 - About the Power Supply

16 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005Specifications 1734-EP24DC POINT I/O 24V dc Expansion Po

Strona 9 - Remove the Power Supply

POINT I/O 24V dc Expansion Power Supply 17Publication 1734-IN058B-EN-P - June 2005General SpecificationsSpecification ValuePower Consumption 9.8 W

Strona 10 - Replace the Power Supply

18 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005Emissions CISPR 11: Group 1, Class AESD Immunity IEC6100-4-26 kV

Strona 11 - Wire the Power Supply

POINT I/O 24V dc Expansion Power Supply 19Publication 1734-IN058B-EN-P - June 2005Current Derating for MountingEnvironmental Specifications1.31.00

Strona 12 - 12/24Vdc Wiring

2 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005Important User InformationSolid state equipment has operational c

Strona 13 - Example of Continuing Power

ö Publication 1734-IN058B-EN-P - June 2005 PN 957955-68Supersedes Publication 1734-IN058A-EN-P - August 2000 Copyright © 2005 Rockwell Au

Strona 14 - Publication

POINT I/O 24V dc Expansion Power Supply 3Publication 1734-IN058B-EN-P - June 2005Preventing Electrostatic DischargeATTENTIONThis equipment is sens

Strona 15

4 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005Environment and EnclosureATTENTIONThis equipment is intended for

Strona 16 - Specifications

POINT I/O 24V dc Expansion Power Supply 5Publication 1734-IN058B-EN-P - June 2005North American Hazardous Location Approval The following informat

Strona 17 - Environmental Specifications

6 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005European Hazardous Location ApprovalEuropean Zone 2 Certificatio

Strona 18

POINT I/O 24V dc Expansion Power Supply 7Publication 1734-IN058B-EN-P - June 2005 ATTENTIONDo not connect 120/240V ac to the 1734-EP24DC terminal

Strona 19 - Current Derating for Mounting

8 POINT I/O 24V dc Expansion Power Supply Publication 1734-IN058B-EN-P - June 2005About the Power SupplyThe expansion power supply passes 24V dc fi

Strona 20 - Certifications

POINT I/O 24V dc Expansion Power Supply 9Publication 1734-IN058B-EN-P - June 2005Install the Power Supply To install the expansion power supply on